Estimation of DC Current Distribution in AC Power System Caused by HVDC Transmission System in Ground Return Status

ZHANG Bo,ZHAO Jie,ZENG Rong,HE Jin-liang,CUI Xiang
DOI: https://doi.org/10.3321/j.issn:0258-8013.2006.13.015
2006-01-01
Abstract:The HVDC transmission system maybe operated in ground return status when the system is in debug or failure. If the ground return current of the HVDC system is large enough, some transformers in AC system may be under DC bias. In this paper, a numerical method is presented to calculate the DC current distribution in AC power system caused by a HVDC system. The method of moments is used to calculate the electric fields in complex earth structure caused by all the grounding systems including the DC grounding electrodes, the AC substation grounding systems, and the long metal pipe lines. The circuit equations are coupled to the moment method to combine the AC transmission lines with the grounding systems. Current distribution of the power system above 220 kV around Chuncheng substation in Guangdong province is analyzed when the Gui-Guang HVDC system is in ground return status. The results are compared with those of testing on site.
What problem does this paper attempt to address?