Influence and Characteristics Analysis of Effect Of the HVDC Ground Return Current on AC System

Rong ZENG,Bo ZHANG,Jie ZHAO,Zong-yuan CAI,Qi WANG,Jin-liang HE,Zheng ZHANG
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.03.011
2009-01-01
Abstract:The HVDC transmission system may be operated in ground return mode when the system is in debug or failure. The disadvantages, such as audible noise, harmonic and oscillation of the transformer in AC systems, are illustrated by analyzing the data of LONG-ZHENG, TIAN-GUANG and SAN-GUANG HVDC system. And field experiments were implemented by measuring the neutral DC current of more than ten transformers when the GUI-GUANG HVDC system was in debugging. Some useful data were acquired and some interesting results were obtained by analyzing these data. Based on the field-circuit theory model, the DC ground current flowing through the neutral point of the transformer was analyzed, and the result verified the feasibility of the theoretical model.