Study on the Influence of HVDC System Grounding Electrode Current on Power Transformer Operation

CAO Lin,ZENG Rong,ZHAO Jie,HE Jin-liang,ZHANG Bo
DOI: https://doi.org/10.3969/j.issn.1001-1609.2006.05.009
2006-01-01
Abstract:When HVDC system operates in monopolar mode and uses the earth as a return path, partial entering ground current may flow into the power transformers, which neutral point grounded, and this will bring a series unfavorable consequences to system operation and transformer. Using electromagnetic coupling method, this paper establishes model of the single-phase transformer with considering the variation of load, and analyzes the effects of such DC current on a single-phase core-form power transformer, such as increment of current harmonics and DC flux in the iron core. The simplified transformer model, under unloaded condition, is analyzed based on analytic method to verify its validity. Furthermore, the influence of different transformer operation status has also been discussed. The simulation results indicate that lower operation point can be more advantageous against the DC bias effects.