Influence of DC Transmission on Transformers in AC System

MEI Gui-hua,XU Bai-yu,WANG Xiao-mao,Deng zhi,LIU Chun-quan
DOI: https://doi.org/10.3969/j.issn.1007-290x.2006.01.001
2006-01-01
Abstract:This paper lists a mass of field test data during the commissioning of the three high voltage direct current(HVDC) transmission systems of Tianshengqiao—Guangzhou,the Three Gorges—Echeng in Guangdong,and Gaopo in Guizhou—Zhaoqing in Guangdong.The analysis of these data shows that the monopolar ground circuit operation mode or the bipolar asymmetric mode of HVDC transmission system has great impact on the noise and neutral line direct current of transformers with earthed neutral point and the harmonic voltage of the AC system,and is likely to damage power equipment in serious cases.This conclusion has vital referential value to the design,construction and operation of HVDC system as well as the adoption of corresponding measures for AC system.