Review and Prospect on Influence of Grounding Electrode Current in HVDC System and Its Suppression Method
Lei SU,Dandan ZHAO,Chenzhao FU,Xin XUE,Lingyu ZHU
DOI: https://doi.org/10.3969/j.issn.1673-7598.2017.03.006
2017-01-01
Abstract:When HVDC system works as monopole ground return mode,the grounding electrode will inject the DC current of more than 1000 A into ground,which will cause the DC current flowing through the grounded natural point of transformer in AC system.The DC current will form return circuit via AC power equipment and transmission lines,which will lead to the DC bias of the transformer,rising of ground potential,corrosion of metal components and etc.To solve the problems presented above,the researches on the influence of grounding electrode current and its suppression method in HVDC System are carried out at home and abroad.After introducing the generation mechanism of the current flowing through natural point in ac system and its damage,this paper reviews the research status on the distribution of ground surface potential and underground current caused by the grounded electrode current,summarizes respectively the methods for calculating the ground surface potential based on Green function and differential equation,and analyzes the factors influencing the distribution of the ground surface potential and underground DC current.And then,the paper summarizes the methods used at home and abroad to suppress the current flowing through natural point based on resistive,capacitive and compensating principles,and introduces the working principles and design schemes of suppression installations.At last,the paper analyzes the shortcomings of present research and looks forward to future study trends.