Evaluation of impressed potential on buried pipeline near HVDC grounding electrode considering polarization effect

Bo Zhang,Fangyuan Cao,Xiaobo Meng
DOI: https://doi.org/10.17775/CSEEJPES.2020.05870
IF: 6.014
2021-01-01
CSEE Journal of Power and Energy Systems
Abstract:When a long distance HVDC transmission system discharge current into the earth through its grounding electrode, ground potential difference appears in a large area. And hence part of the DC current may flow into nearby pipeline which may be dangerous to the equipment and personnel, and may aggravate corrosion. In this paper, an equivalent circuit based on method of moments is put forwards to calculate the current and potential distributions along the pipeline with damaged anticorrosive coating. The current-dependent electrochemical polarization potential between soil and the metal pipe due to the damage of the anticorrosive coating is taken into account by using the Newton-Raphson scheme. The circuit is verified by reduced scale experiment. With the circuit, the effect of the damaged anticorrosive coating on the leakage current and the pipe potential with respect to soil along the pipeline is analyzed.