Analysis of Insulation Methods to Reduce Influences of DC Grounding Electrode on Pipeline

Xiaobo MENG,Fangyuan CAO,Yongli LIAO,Ruihai LI,Bo ZHANG
DOI: https://doi.org/10.13336/j.1003-6520.hve.20171127011
2017-01-01
Abstract:When a DC power transmission system is operated under monopolar ground circuit mode,thousands ofamps of current can be injected into the ground from the DC grounding electrode,which will form a wide range of potential gradient in the ground,leading to a high potential on the buried metal pipe,and seriously affects the safe operation of oil and gas pipelines in the vicinity.We established an equivalent circuit model for the coating and insulation joints of the pipeline by the idea of numerical analysis of the grounding system.Through numerical simulation,the effectiveness and regularity of the two measures to reduce the influences of the DC ground current on the pipeline were studied,the optimized solutions to arrange the insulating joints were also studied.The research results show that,as the insulation resistance of the coating has already been very high,increasing the resistivity or thickness of the insulating coating to reduce ground current effect will have little effect.When there are damaged points on the pipeline,reinforced insulation coating will increase the current flowing through the damaged points,thus increasing the corrosion rate of the pipeline.Installing insulating joint on the pipeline can significantly reduce the influences of the ground current on the pipeline,which will greatly reduce the risk of pipeline coatings and cathodic protection equipment.The research results can provide a reference for reducing the influences of DC grounding electrode on pipeline.