Research on Vertical Grounding Rod Performance

YANG Fang-yuan,WANG Sen,LI Zhi-zhong,ZHANG Bo,ZENG Rong
DOI: https://doi.org/10.3969/j.issn.1673-7598.2010.01.002
2010-01-01
Abstract:Grounding grid is an important facility to ensure substation safety.The vertical grounding rod is a common measure to reduce the grounding resistance.Typical grounding grids in 110 kV,220 kV,500 kV and 1000 kV substation are selected in the paper.For uniform soil,the vertical grounding rod's reduction in resistance is studied on grid area,the vertical grounding rod length and the number.The ratio of the vertical grounding rod length and grounding grid's diagonal length is proposed to represent a clear description of the link between the vertical grounding rods' resistance reducing rate in grounding grids of different sizes.For the double-layer soil,grounding grids are divided into two categories including the large area and the small area.The paper also studies the effect of reflection coefficient and the upper soil thickness on the resistance reducing rate of the vertical grounding rod.The results show that the vertical grounding rod is particularly effective for the grounding system buried in the soil with a low-resistivity layer down.The results and conclusions of this paper can provide reference for the engineering practice.
What problem does this paper attempt to address?