Research on Neutral Point Grounding via Resistance for 66 kV Distribution Network

NIE Hong-zhan,ZHAO Fu-wei,YUAN Gui-dong,SONG Lai-sen,LI Yu-ling
DOI: https://doi.org/10.3321/j.issn:1000-3673.2007.14.015
2007-01-01
Abstract:Due to the defects of adopting traditional grounded neutral system in 66kV distribution network, in this paper it is proposed to adopt neutral point grounding via resistance for 66kV distribution network located in a certain city center, while the factors such as overvoltage, relay protection, communication interference and so on are comprehensively considered. By use of Matlab toolbox, a distribution system using this grounding mode is simulated and the value of grounding resistance at the neutral point is determined. The impact of neutral resistance value on arcing ground overvoltage is emphatically analyzed. Calculation results show the proposed grounding mode can effectively restrain the arcing ground overvoltage, ensure the selectivity of relay protection, enhance the action sensitivity of protection devices.
What problem does this paper attempt to address?