Abstract:Considering the breakdown explosion of reactive compensation capacitors in Honggou 500 kV substation,the destroyed capacitor was dissected and analyzed carefully.The results show effectually that capacitor interior over voltage is one of the main reasons of insulation destroying.To guarantee the safe operation of capacitors,the imbalance current protection should act correctly.Based on the calculation and measurement of imbalance current,the number of interior penetrated components can't exceed 4,and the setting value should be modified to 0.93~1.00 A.