Analysis on Contamination Discharges of External Insulation in 500 Kv Gangcheng Substation

刘平原,王黎明,何宏明
DOI: https://doi.org/10.3969/j.issn.1674-0629.2009.z1.019
2009-01-01
Abstract:The cause of serious discharges of external insulation in 500 kV Gangcheng Substation is analyzed through of insulator surface contaminations surveys, artifical cantamination laboratory tests and the electric-field calculations, and it is concluded that sugar-containing contaminations attached to the equipments in the substation result in the electric-field increase of some regions of the external-insulation surfaces, and thus lead the strong and widespread discharge.The discharge mechanism of the sugar-containing and non sugar-containing contaminations are studied with artifical cantamination laboratory tests, at the same time the effect and long-term performance of the anti-pollution coating to weaken the external-insulation discharges in the substation are discussed too.Based on the electric-field calculation results, this paper proposes some suggestions for the corona ring parameters selection of the insulator strings to improve the electric-field distribution.