Equivalent Investigation of Natural Contamination and Artificial Contamination Test

Liming Wang
2010-01-01
Abstract:It is necessary to carry out comprehensive pre-researches on external insulation to ensure these projects to be operated safely.In order to provide a scientific reference for the constructions of DC transmission lines in high altitudes,the difference of natural contamination and artificial contamination tests of DC composite insulators were carried out at high altitude area(1970 m),Kunming China.In the experiment,the condition studied were ρNSDD,distributing of nastiness and components of salt.According to the results of the tests,the influence of the factors(ρNSDD,distributing of nastiness,components of salt,etc) on the flashover characteristics of insulators was studied.It was found that:the relationship between the modified coefficient of ρNSDD and ρNSDD was a negative power function in the condition of ρESDD remained constant and the ρNSDD of insulators was no more than 1.0 mg/cm2 ;the flashover voltage increased with the extent of un-uniform pollution distributing in the condition of ρNSDD keeping constant;the relationship between the modified coefficient of the different components and the proportion of CaSO4 was a exponent function in the condition of ρESDD remained constant.These results would be useful in calculating the DC flashover voltage of composite insulators in the condition of natural contamination,and can also be treated as basis for outdoor insulator selection of transmission lines.