DC Pollution Resistance Performance of Composite Insulators in High Altitude

GUAN Zhi-cheng,ZHAO Feng,ZHANG Fu-zeng,YANG Hao-lin,WANG Li-ming,WEN Hua,MA Yi
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.08.022
2009-01-01
Abstract:In order to research the pollution resistance performance (pollution flashover and raining flashover) of composite insulator and its influential factors for composite insulator in natural high altitude in China and aboard,based on these pollution flashover tests and raining flashover tests of contaminated composite insulators under different conditions (component of soluble material,distribution,ESDD and NSDD) in natural high attitude (1970 m),the influence of pollution conditions on DC pollution flashover performance was analyzed systematically. The influential factors (ESDD and different precipitation rates) of raining performance were comparatively analyzed. The results show that,pollution flashover voltage decreases with the increase of ESDD by a negative power function as well as NSDD. The increasing percentage of CaSO4 leads to the higher DC contamination flashover voltage. The relationship between flashover voltage and non-uniform pollution ratio of up-and-down surface is presented. The experimental results also indicate that the relationship between ESDD and raining flashover voltage obeys negative power function and raining voltage decreases with the increasing precipitation rate. These results and conclusions can be used in the design of DC transmission line in high altitude.
What problem does this paper attempt to address?