Pollution Flashover Performance of Converter Station Post Insulators at High Altitude Area

张楚岩,关志成,张福增,王黎明
2012-01-01
Abstract:In this paper,the previous research work of the polluted outdoor insulating performance of converter stations post insulators is summarized.Moreover,according to the peculiar technology problems of UHV DC projects' external insulation in China,such as high altitude and heavy pollution etc.,the pollution flashover performances of full-size ±800 kV post insulators made of both porcelain and composite for UHVDC converter stations are reported and investigated by artificial contamination tests at actual high altitude area.Furthermore,the pollution flashover voltages of post insulators in fog and under rain in the same pollution level conditions are compared.Meanwhile,discussion and comparison are presented for the research results of previous work and this paper.The results of artificial contamination tests show that the rod diameter and the shed configuration has a significant influence on pollution flashover performance of post insulator;the relationship between the pollution flashover voltage and the insulation distance is approximately linear at actual high altitude area for post insulators;the outdoor insulation design of post insulators should give priority to the pollution flashover voltages in fog,since the voltages are lower in rain.
What problem does this paper attempt to address?