Study on Selection Method of External Insulation and Insulator Type Selection for 750 Kv Transmission and Transformation Equipment in High Altitude Area

GUAN Zhi-cheng,WANG Li-ming,JIA Zhi-dong,ZHOU Jun
DOI: https://doi.org/10.3969/j.issn.1674-3814.2007.07.001
2007-01-01
Abstract:Polluted external insulation is the controlling factor for the selection of external insulation of the electrical equipments used in the 750 kV transmission lines. The problem has become more serious in high altitude areas with lower air pressure. According to the requirements of the 750 kV demonstration project in China, four types of 210 kN and 300 kN porcelain insulators, four types of 210 kN and 300 kN glass insulators and three kinds of the post insulators with different shed types have been tested in different altitudes and different pollution levels. Meanwhile, the flashover characteristics of the composite insulators in different altitudes have been studied. Comparisons of flashover characteristics between the post insulators covered with RTV or without RTV are carried out. Specific creepage distance method and withstand voltage method are adopted to select the suspension and post insulators in different pollution levels and different altitudes. As a result, the three-shed-suspension insulators and two-shed-suspension insulators are recommended for the transmission lines. The three-shed-post insulators with deep grooves are recommended for the substations. The results have shown that the pollution resistance performances of composite insulators have advantages over that of the porcelain and glass insulators. So they are recommended in high altitude area with heavy pollution.