Study on Flashover Performance of Post Insulator for 750 Kv Transformer Substation in High Altitude Area

WANG Li-ming,LONG Biao,ZHOU Jun,MAO Su-chun,ZHANG Fu-zeng,JIA Zhi-dong,GUAN Zhi-cheng
2005-01-01
Abstract:Artificial contamination tests were carried out for three types of porcelain post insulators in four air pressure cases corresponding to the altitude from 0m to 3000m and in two typical kinds of equivalent salt deposit density (ESDD). The test results indicate the regularity of the flashover voltage of polluted post insulators at different altitudes. The heights of post insulators, which match the 750kV transformer substation, were put forward accordingly.