DC Pollution Flashover Performance of Ultra High Voltage Parallel Double Insulators in High Altitude Area

SONG Lei,ZHANG Fuzeng,LIANG Xidong,LIAO Yifan,LI Ruihai
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.06.014
2013-01-01
Abstract:To guide operation and maintenance for established ±800 kV ultra-high voltage direct current(UHVDC) transmission lines,and to provide references for external insulation design of future UHVDC projects,we studied the pollution flashover performance of parallel double insulator strings(Ⅱstrings) in high-altitude areas.Tests were performed on samples of XZP-300 porcelain insulators and one major,one middle and four minor sheds shaped composite insulators.The probability distribution of flashover voltages under artificial contamination test was explored.Moreover,the difference between flashover voltages of Ⅱ strings and single Ⅰstrings was analyzed,and the influence of spacing on the flashover voltage of Ⅱ strings was investigated.The results showed that the flashover voltages of Ⅱ strings and Ⅰ strings installed by up-and-down method in high-altitude areas were distributed normally.When the equal salt density varied from 0.03 to 0.2 mg/cm2,the one-unit flashover voltages of porcelain Ⅱ strings and porcelain single Ⅰ string varied from 19.6 to 5.8 kV and from 20.5 to 6.9 kV,respectively.When the equal salt densities varied from 0.05 to 0.2 mg/cm2,the per-meter flashover voltage of porcelain Ⅱ strings and porcelain single Ⅰ string varied from 105.6 to 38.7 kV and from 109.9 kV to 43.1 kV,respectively.When the spacing exceeded 20 cm,further enlarging spacing had no significant effect on the flashover voltage of Ⅱ strings.
What problem does this paper attempt to address?