External Insulation Characteristics of Dc Transmission Line at High Altitudes

ZHANG Fuzeng,WANG Liming,GUAN Zhicheng,ZHAO Feng,YANG Haolin,WANG Xin,MAO Yingke,LIU Zhen
DOI: https://doi.org/10.3321/j.issn:1000-0054.2008.07.004
2008-01-01
Abstract:Artificial pollution experiments was carried out with up-and-down method under direct current(dc) voltage in natural high altitude areas(1970 m) to analyses the effect of insulator profiles and suspension patterns on flashover characteristics of porcelain,glass,and composite insulators.The experimental results indicate that the arc development paths differed greatly for the various suspension patterns.The flashover voltage was lowest for the Y-strings due to the configuration facilitating the development of arcs.The flashover voltage in the V-strings was 7% better than with I-strings.The insulator profiles have a significant effect on the dc flashover performance.Although the flashover voltage of the composite insulator is much higher than that of the glass and porcelain insulators,the flashover voltage can be further increased by more than 20% by optimizing the shed parameters.Thus,the flashover voltage was not only determined by the leakage distance,bat also by the insulator profile and the suspension patterns which should be taken into consideration in outdoor insulation designs.
What problem does this paper attempt to address?