DC Flashover Performance of ±800 Kv Composite Post Insulator in High Altitude Area

YANG Hao-lin,ZHANG Fu-zeng,ZHAO Feng,WANG Li-ming,GUAN Zhi-cheng
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.04.007
2009-01-01
Abstract:In order to provide an experimental basis for extra-high voltage DC external insulation design, DC contamination was tested by constant voltage up-and-down method in the area of actual high altitude(1970 m). The DC flashover performance of 4 types of composite post insulator and 2 types of ceramic post insulator under different ESDD, NSDD, insulator material and shapes were studied. The tests were carried out at YunNan Electric Power Research Institution, using a high speed camera to record the flashover arc and an instrument developed by Tsinghua University to record the leakage current in the tests. The result indicates that DC flashover voltage decreases by a power function when ESDD or NSDD increases. The influences of ESDD and NSDD on voltage are independent with each other and the formula for a certain type of insulator is proposed by the least square method. Comparison among insulators shows that DC flashover performance of composite post insulators is better than ceramic post insulators. Besides, DC flashover voltage of unit insulation length decreases when mandrel diameter increases.