Flashover Performance of Different Suspension Styles of Insulators in High Altitude

GUAN Zhi-cheng,LONG Biao,ZHANG Fu-zeng,MAO Su-chun,WANG Li-ming,WEN Hua,MA Yi
DOI: https://doi.org/10.3969/j.issn.1003-6520.2007.10.001
2007-01-01
Abstract:In the area of high altitude in Kunming(1 970 m),for two different types of DC porcelain insulators: XZP1-300 and XZSP-300,the artificial contamination tests are carried out in different types of suspension styles(I-,V-,Y-string) to study the influences of suspension styles on flashover performance of DC porcelain insulators,as well as to provide evidences for insulation selection for UHV transmission lines.V strings include three different angles: 60°,90° and 120°.The angle of the top-half of Y string is 90. The arcing behavior on natural polluted insulator surfaces was studied using a PCI-2000S high speed camera.The experimental results show that the DC arcs play an important role in the flashover performances since the DC arcs levitate more easily from the porcelain surfaces at high altitudes than at sea level.According to the photos of the flashover process,the factors(suspension style,insulator shape and ESDD) how to influence the development of the electric arc is studied.And the reason of the difference is explained.A suggestion that V-string should be used in heavy polluted and I-string in others is obtained.
What problem does this paper attempt to address?