Study on Selection of 750 Kv Transmission Line Insulators in High Altitude Area

WANG Li-ming,ZHANG Fu-zeng,ZHOU Jun,MAO Su-chun,LONG Biao,JIA Zhi-dong,GUAN Zhi-cheng
DOI: https://doi.org/10.3969/j.issn.1004-9649.2006.01.003
2006-01-01
Abstract:For four different types of porcelain insulators with 210 kN,300 kN and four different types of 210 kN,300 kN glass insulators,the artificial contamination tests were carried out in four pressure cases corresponding to the altitude from 0 m to 3 000 m and in two typical kinds of equivalent salt deposit density(ESDD).The tests show that the flashover voltage of polluted insulators regularly decreases with the increasing of the altitude.And the flashover performance of No.4 and No.2 porcelain insulators' is better than other insulators,so No.4 or No.2 porcelain insulator is recommend in this paper.At last,the pieces of No.4 and No.2 insulators for 750 kV transmission line at different altitude are given and are proved in this paper.