Study on methods of preventing pollution flashover and wet flashover for 750 kV lines in high altitude area

Zhi-cheng GUAN,Hai-feng GAO,Jun ZHOU,Li-ming WANG,Jie YANG,Zhi-dong JIA
DOI: https://doi.org/10.3969/j.issn.1004-9649.2005.12.006
2005-01-01
Abstract:The first 750 kV transmission line was built up in northwest China,and the most parts of this line lain in high altitude area.The artificial pollution test was carried out on a kind of 35 kV composite insulator,two kinds of cap and pin insulators and a kind of post insulator with and without RTV coating in different pressure condition corresponding to the altitude from 0 m to 3 000 m.The results show that,though the flashover voltage of composite insulator and RTV coated insulator decreases with the increase of altitude,which is similar to normal porcelain insulator,the anti-pollution flashover ability of them are much better than those of porcelain insulators.According to the latent climate and environment in high altitude area,the hydrophobicity of silicone rubber was also studied in the conditions of low temperature,low pressure and high humidity.It is found that the influences of low temperature and high humidity are much severer than that of low pressure.Further more,the paper analyzed the common characteristics of insulators,on which wet flashover happened.Some suggestions on improving the ability of preventing wet flashover were given.
What problem does this paper attempt to address?