Abstract:The external insulation is one of the most important technological issues in the construction of UHVAC transmission projects.We mainly studied the optimal design of composite insulators' shed.Using the results of artificial contamination test for 14 composite insulators with different profiles as well as the results of simulation analysis on the contamination depositing characteristics of composite insulator,we optimized the profiles of the composite insulators in order to improve overall performance of the composite insulators.Thereafter,flashover voltages of composite insulators can be enhanced greatly,and the composite insulators have better contamination depositing characteristics.Therefore,the dimension of towers will be decreased and the cost of transmission systems will be reduced,especially in heavy pollution areas.Accordingly,this work can provide theoretical support of the external insulation design and the selection of insulators for 750 kV EHV AC,1000 kV UHV AC transmission projects.
What problem does this paper attempt to address?