Reliability of Composite Insulators Used for UHV AC/DC Transmission Line

SU Zhi-yi,YIN Yu,ZHOU Jun,GAO Hai-feng,DENG Tao,LIANG Xi-dong,WANG Jia-fu
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.10.032
2009-01-01
Abstract:Because of the higher voltage and capability,length(creepage distance)and mechanical performance of composite insulator used on UHV AC/DC system will be significantly increased.In present study,the method how to improve the performance of core rod and shed material used in composite insulator for UHV AC/DC lines is introduced,the creepage distance of the composite insulators is selected,and corona ring is optimized for improving its axial electrical field distribution.To increase the strength of the core rod,the 1.2 times specified mechanical load(SML)test is added.For increasing resistance to conductor galloping and sleeting jump induced by ice-shedding,impact dynamic load test is also added.In order to ensure the reliability of V type string used on composite insulator,the end-fitting type is changed to the ring-ring connection.
What problem does this paper attempt to address?