Safety Coefficient of Composite Insulators Tension Strings for 500 Kv AC Transmission Lines

王黎明,汪创,李庆峰,傅观君,侯镭,关志成
2012-01-01
Abstract:The traditional porcelain tension insulators for 500 kV AC transmission lines have a lot of disadvantages such as overweight,ill performances of pollution flashover,faulty insulators,and low economic benefit,so new technological measures should be taken.Due to excellent pollution flashover performance,light weight,and high mechanical strength,composite insulators are widely used as suspension strings on high voltage transmission lines.The key problem of composite insulators tension strings is the safety coefficient.By comparative study,we used the nonlinear dynamic analysis method on the overhead transmission line,and calculated the dynamic action force of composite insulators tension strings,under string-breaking,ice-shedding,galloping and typhoon.Result shows that,the impact coefficient of tension strings is not higher than that of suspension strings,so the safety coefficient 3 of composite insulators tension strings is reasonable.
What problem does this paper attempt to address?