Influence of High Altitude Factor on the Contamination Flashover Performance of Insulators

关志成,李健,周军,王黎明
2012-01-01
Abstract:According to the urgent needs of the investigation of the outdoor insulation performance in high altitude for the power transmission from west to east and Tibet interconnection,we summarize the research works on the contamination performance of insulators under low pressure both in home and abroad,and emphatically introduce the recent research achievements in the field in China.It is found that the influence of pressure on the contamination flashover voltage can be evaluated by aexponent n.A statistic analysis shows that the average value of n is 0.49 for suspension insulators and 0.48 for post insulators under AC condition while the corresponding values are 0.27 and 0.42,respectively,under DC condition.A further discussion about the mechanism of pollution flashover voltage decrease under low pressure is presented.It is believed that the decrease of AC U-I characteristic and the arc bridging among sheds are the main reasons for the decrease of the voltage.Then,the physical meanings of the characteristic parameters n and K which demonstrate the influence of pressure and altitude are discussed.It is concluded that the parameter K has a definite physical meaning.Finally,the degrees of altitude affecting the corona inception voltage,air gap breakdown voltage and pollution flashover voltage are compared,and the results show that the decrease degree of pollution flashover voltage is not the most serious if the shed profile is reasonable.
What problem does this paper attempt to address?