Design And Test Of Unified Power Flow Controller Protection Circuits

Yimu Guo,Daozhuo Jiang,Yufen Wang,Feng Chen
DOI: https://doi.org/10.1109/ISGT.2016.7781179
2016-01-01
Abstract:In this paper, the overcurrent and overvoltage mechanism of unified power flow controller (UPFC) during its operation in high voltage system is analyzed, and a set of detailed protection circuits is designed for UPFC. This protection circuits inserts charging resistors automatically in the shunt side of the UPFC, and removes it after uncontrolled charging completes in the start-up phase of UPFC. When a short-circuit fault occurs, the Fault Current Limiter (FCL) is inserted immediately to limit the fault current. The outlet of shunt converter is shorted with no delay to isolate the large voltage and current when overvoltage of the dc capacitor occurs. The proposed circuits are applied to a 10kV/lMVA UPFC. Experimental results prove the reliability and feasibility of the protection circuits which operates automatically, ensures the safe operation of UPFC, and does not affect the normal function of UPFC.
What problem does this paper attempt to address?