Parameter design and optimization of unified power flow controller with fault current limiting

Fan GUI,Daozhuo JIANG,Wentao L(U),Zhongshan TIAN,Zhaolin WU
DOI: https://doi.org/10.3969/j.issn.1006-6047.2013.11.028
2013-01-01
Abstract:The mathematical short circuit model of UPFC-FCL(Unified Power Flow Controller with Fault Current Limiting) is improved,which takes the current limit of power system,the maximum compensation degree of unified power flow controller,the voltage and current limits of IGBT and the DC voltage limit as its basis. A method for DC capacitor calculation is put forward to ensure the DC capacitor voltage lower than the limit during short circuit. The DC capacitor is added into short circuit current limiting loop and the DC current limiting inductor is optimally selected to enhance the reliability and economy of UPFC-FCL.A 100 V / 3 kV·A UPFC-FCL experimental model is established,which verifies the rationality and validity of the design parameters of UPFC-FCL.
What problem does this paper attempt to address?