Damping channel selection based on damping torque analysis and coordinated design of auxiliary stabilizer for UPFC
Bixing REN,Wenjuan DU,Haifeng WANG,Junhui HUANG,Yan ZHANG,Xiangfeng WANG,Hui CAI
DOI: https://doi.org/10.16081/j.issn.1006-6047.2017.05.010
2017-01-01
Abstract:Based on the research of low-frequency oscillation damping by UPFC (Unified Power Flow Controller),DTA(Damping Torque Analysis) method is extended to the multi-machine power system with UPFC.According to the mechanism of damping torque generation,transmission and distribution of stabilizer,DTA index is adopted to select the best damping channel of UPFC.A four-generator two-area system is taken to verify its rationality.Since multiple stabilizers can be added to multiple damping channels of a UPFC for suppressing multiple oscillation modes,a method of coordinated design is proposed for the multiple stabilizers of a UPFC,which selects multiple damping channels of UPFC according to DTA index,applies HookeJeeves method to coordinate the equivalent damping coefficients,and uses the phase compensation method to design the parameters of multiple stabilizers.Simulative result shows that,the proposed method can effectively damp multi-mode oscillations(including inter-area mode and local mode).