Influence of Tower Grounding Lightning Currents on Surrounding Fish Ponds and Protective Measures

ZHAN Qinghua,CHEN Zhucheng,LI Hongtao,LIU Yijun,MEI Cheng
DOI: https://doi.org/10.3969/j.issn.1007-290X.2018.003.021
2018-01-01
Abstract:In allusion to the phenomena of massive fish death in a pond near to the tower after thunderstorm in a certain area of Guangdong,this paper makes simulation and modeling for the accidental tower of 220 kV Luodan Ⅱ line.It verifies ac-curacy of the model based on CDEGS software and studies relationships between fish body lengths and current flow angles of the fish in the electric field and current densities of the fish.Meanwhile,it analyzes electromagnetic influences of different surrounding soil resistivities and distances from the fish pond to the grounding device (thereafter as fish pond distances)on the fish.Corresponding research indicates as the length of fish increases,the center current density of fish changes smaller, and as the current flow angle becomes larger,the center current density of fish becomes smaller which reaches the minimum as the angle is 90°.In addition,high soil resistivities may intensity trend of impact current scattering into the fish pond and increase influence of fish pond distances on current densities of fish.Finally,it presents a transform scheme of installing the insulating shield and vertical grounding electrode for the horizontal grounding electrode according to actual engineering.