Influence of the Ground Material on the Ground Impedance of Large-scale Hydropower Plant
ZHANG Bo,JIANG Yukuan,YANG Jianjun,LI Xiaofeng,CHEN Shuiming
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.04.029
2013-01-01
Abstract:Due to the large scale,scattered arrangement,loose connection,and non-uniform soil of a grounding system of hydroelectric power plant,the longitudinal impedance characteristics of grounding materials may obviously affect the grounding resistance.Consequently,according to the distribution characteristics of grounding system in hydroelectric power plants,we established a voltage-different grounding system model by taking the effects of the longitudinal impedance into consideration and using the field-circuit coupling method,and analyzed the influence of commonly used grounding materials such as copper and steel on the ground impedance of large-scale hydropower plant with different soil models and different current injected points.Moreover,we put forward a measure to reduce the ground impedance by using suitable material.The analysis results show that,although grounding material has little effect on the grounding resistance of substations,its effect on that of hydropower grounding system is remarkable.Traditional formula for analyzing the grounding system is not suitable for hydroelectric power plants,and numerical methods are necessary.When the current injected point is located on bank,the difference of the grounding resistance between copper and steel is up to more than two times.Copper electrode can significantly reduce the grounding resistance of a hydropower plant.It is recommended to use copper conductors to connect different parts of a grounding system,which is both economical and effective.