Experimental Study On Dc Biasing Impact On Transformer'S Vibration And Sound

Hongbin Ma,Jinliang He,Bo Zhang,Rong Zeng,Shuiming Chen,Lin Cao
DOI: https://doi.org/10.1109/ISEMC.2008.4652028
2008-01-01
Abstract:DC biasing current through the neutral point of ac power transformer would lead the power transformer to generate more vibration and sound, this will do harm on power transformers' core pieces or windings and finally will threaten the safe operation of the transformers. This paper described the principle of DC biasing, designed a new DC biasing experiment to analyze how the experimental transformer's vibration and sound change along with the value of DC biasing current or windings voltage and finally some curves were given in order to show the direct connection between vibration peak value, sound pressure and DC current.
What problem does this paper attempt to address?