Field Monitoring and Analysis on Vibration and Noise of 500 Kv Electrical Transformer under DC Current Biasing

陈青恒,马宏彬,何金良
2009-01-01
Abstract:In order to observe the influence caused by the DC biasing current through the neutral point of the power transformer,a new on-line vibration and sound monitoring program was designed with use of both qualified vibration and sound sensors at the same time.The experiment was operated in Huizhou 500 kV substation and a 500 kV single phase electrical transformer was chosen as experimental object.Based on the experiment platform,steady and clear vibration and sound waveform before and after the DC biasing condition was recorded and spectrum analysis was also achieved based on the data monitored.In conclusion,DC biasing is harmful for power transformers and the result of this research provides valuable reference to the on-line vibration and sound monitoring system of transformers.