Effect of DC Magnetic Biasing on the Temperature Rise of High-voltage Winding of Power Transformer

Yun-Yan Xia,Yong-Ming Xu,Yong-Sen Han
DOI: https://doi.org/10.1515/9783110540048-038
2017-11-07
Abstract:The DC magnetic biasing can aggravate the core saturation and increase the temperature in the large power transformer. In this paper, a 240000 kVA/330 kA oil immersible power transformer is taken as a research object to analyze the variation of the temperature rise in the high-voltage windings under DC magnetic biasing. The effect of DC magnetic biasing current on the winding loss is analyzed at first. Using computational fluid dynamics and fluid network of power transformer, the fluid field and the temperature distribution in the power transformer are then obtainned. The results show that the temperature rise is greatly affected by the DC magnetic biasing phenomenon. The calculation method proposed in this paper provides a theoretical basis for the structure optimization and the local over-heating suppression.
What problem does this paper attempt to address?