Application of PR Control in Restraining DC Magnetic Bias for Output Transformer of Inverter

ZHANG Hai-yu,WANG Zheng-shi,CHEN Hui-ming
DOI: https://doi.org/10.3969/j.issn.1001-4551.2011.08.021
2011-01-01
Abstract:The inverter itself,output transformer and AC loads would be influenced greatly by DC magnetic bias for output transformer of inverter which threatens the reliable operation of inverter seriously.Thus,aiming at DC magnetic bias for output transformer of inverter,a simple and applied approach involving PR control achieved by digital signal processor(DSP) was proposed,and according to theoretical researches,the effectiveness was verified by a 50 Hz/3 kW single phase inverter.The experimetal results show that,the effectual restraint of DC magnetic bias for output transformer of inverter can be accomplished successfully.The good performances of dynamic and steady characteristics of the control system are ralized.Its effectiveness is demonstrated through both of them.
What problem does this paper attempt to address?