PRI Control Methodology for Wind Power Grid-connected Inverters in Harmonic Distorted Grid Utility

Fansen TANG,Huipin LIN,Lujun WANG,Zhengyu LYU
DOI: https://doi.org/10.13234/j.issn.2095-2805.2015.4.8
2015-01-01
Abstract:For the problem of low order harmonics caused by nonlinear loads,the impacts of grid voltage on grid current in distributed generation grid-connected inverters are analyzed, and a control strategy that can compensate harmonics and suppress DC bias is proposed. In comparison with traditional PR controller, the proposed PRI controller with an additional integral part obtains a higher gain in low frequency, and the controller has an apparent effort especially for suppressing DC bias. Finally, the PRI controller is verified in a 50 kW three-level inverter. The experimental results show that the PRI controller not only can reduce harmonics of grid current in the steady state but also can suppress DC bias rapidly in a dynamic process. The PRI controller is suitable for DGs since they typically contain low order harmonics which caused by nonlinear loads.
What problem does this paper attempt to address?