Investigation and Restraining of Magnetic Bias for the Output Transformer of Full Bridge Single-phase Inverter Circuit
LIU Gang,ZHANG Dong-lai,ZENG Jian-you
DOI: https://doi.org/10.3969/j.issn.1000-100x.2006.03.029
IF: 5.967
2006-01-01
IEEE Transactions on Power Electronics
Abstract:The main factors resulting in magnetic bias of the output transformer of full bridge SPWM inverter are analyzed,including the direct-current component of control system,zero floating,inconsistent characteristic of transistor,dynamic response of system,and so on.Then,one solution is proposed to overcome the problem.The solution is that,firstly,we can detect the input current′s DC component value of the transformer,and put it through isolate and filter modules.Secondly,we can feedback the value to the reference voltage in order to adjust the width of SPWM pulse.The experimental results on an 80kVA Plant UPS show that the method is applicable to many occasions such as the UPS is feeding with resistance load,rectifier load and half-wave load.When the UPS is feed with resistance load,the DC component input of current values will change from 15.4A(without magnetic bias method) to 7.1A;when the UPS is feed with rectifier load,the input current′s DC component values will change from 15.8A(without magnetic bias method) to 5.5A.From the experiments,we can get the conclusion that this project can be effective for restraining magnetic bias for the output transformer of full bridge single-phase inverter circuit and it is easy to realize.