Mechanism and Application Analysis of Rectification-bridge Type Over-voltage Suppression Equipment

GUAN Yong-gang,LIU Wei-dong,QIAN Jia-li,CHEN Shui-ming
DOI: https://doi.org/10.3321/j.issn:1000-1026.2009.09.015
2009-01-01
Abstract:A rectification-bridge type over-voltage suppression equipment can significantly suppress over-voltage occurred during a no-load electric furnace transformer interrupting.However,the mechanism and application of the equipment have not been systematically analyzed.Based on electromagnetic transient analysis,over-voltage suppression mechanism of the equipment is analyzed.The equipment absorbs electromagnetic energy stored in the circuit with high-capacity electrolytic capacitor after current chopping,and the over-voltage is also limited by small leakage inductance of the transformer winding.In typical condition,the over-voltage can be limited to 1.15 rated.In addition,an estimation formula of over-voltage is derived as well.The main influencing factors,such as short circuit impedance,capacity,chopping current,and terminal-to-earth capacitance of the transformer,to the over-voltage are evaluated,It is concluded that the less the short circuit impedance or the larger the capacity of the transformer,the smaller the over-voltage.