Influence on Switching Capability of HV Circuit Breakers by Employing Rectifier Type Fault Current Limiter

QIAN Jiali,GUAN Yonggang,XU Guozheng,LIU Weidong
DOI: https://doi.org/10.3321/j.issn:1000-0054.2005.10.005
2005-01-01
Abstract:The rectifier type FCL not only reduces the amplitude of short circuit currents but also changes their waveform which seriously affects the making and breaking capability of HV circuit breakers.Therefore,it must be carefully to selected and test circuit breakers.An electrical-magnetic transient analysis was used to analyze 7 factors affecting the making and breaking process.These factors are the breaking current,the peak short circuit and making current,the breaking current for the second and third poles to clear,the decay rate as the current approaches zero,the arc energy,the rise rate,and amplitude of the recovery voltage.The results indicate that the decay rate as the current approaches zero may increase 600%,the arc energy may increase 50% and the peak making current and the short circuit current may be reduced by 40%.All these factors seriously affect the making and breaking capability of HV circuit breakers.
What problem does this paper attempt to address?