Study on reliability improvement of current-transferring type HVDC circuit breaker

Feng Xu,Yi Lu,Jianhua Li,Qiatt Chen,Peng Qiu,Daozhuo Jiang
DOI: https://doi.org/10.1049/cp.2019.0262
2019-01-01
Abstract:The current-transferring type HVDC circuit breaker (CT-DCB) can reduce the investment cost and optimize the equipment utilization value. However, the operation reliability of the CT-DCB is lower than the hybrid HVDC breaker (H-DCB). In order to improve its reliability, the reliability improvement methods based on the equipment level and the system level are proposed. In the equipment level, a new diode clamped CT-DCB is proposed to improve the device reliability. In the system level, a redundant configuration strategy is proposed to improve the dc fault isolation capability and the backup protection capability. In order to verify the effectiveness of the proposed scheme, a simulation model of four-terminal HVDC transmission system with the diode clamped CT-DCB is established in PSCAD/EMTDC. Simulation results prove validity and feasibility of the proposed scheme.
What problem does this paper attempt to address?