Adaptive reclosing strategy for the mechanical DC circuit breaker in VSC-HVDC grid

Bin Li,Qiyang Mao,Jiawei He,Ye Li,Tonghua Wu,Wei Dai,Xindong Li,Qingyuan Yu
DOI: https://doi.org/10.1016/j.epsr.2020.107008
IF: 3.818
2021-03-01
Electric Power Systems Research
Abstract:<p>The overhead line has wide application prospect in the future VSCHVDC grid. However, compared with the dc cable, the fault probability (especially the nonpermanent fault), is much higher on the overhead line. To enhance the system power supply reliability, effective reclosing strategy must be configured for the DCCBs. The existing automatic reclosing strategy recloses the DCCB directly, resulting in serious secondary overcurrent damage to the dc grid under permanent fault. In a 500 kV dc grid, this secondary overcurrent is up to about 10kA. Therefore in this paper, the mechanical DCCB residual voltage characteristics under permanent and nonpermanent faults are analyzed. According to the obtained characteristic, the adaptive reclosing strategy is proposed for the mechanical DCCB in VSCHVDC grid. The theoretical analysis indicates that, the proposed reclosing strategy can not only reliably identify the fault property, but also limit the secondary overcurrent under permanent fault. This means the requirement on the consecutive interruption capability of DCCB is reduced significantly. Finally, simulation cases based on the PSCAD/EMTDC are carried out to verify the correctness of the theoretical analysis, as well as the feasibility and superiority of the proposed reclosing strategy.</p>
engineering, electrical & electronic
What problem does this paper attempt to address?
This paper proposes a new reclosing strategy for mechanical DC circuit breakers (DCCB) in voltage source converter (VSC) high voltage direct current (HVDC) grids. Specifically, the paper aims to address the following issues: 1. **Improving system power supply reliability**: Since overhead lines have a higher probability of non-permanent faults compared to DC cables, an effective reclosing strategy is needed to quickly restore the line in the event of a non-permanent fault. 2. **Avoiding secondary overcurrent damage**: Existing automatic reclosing strategies directly reclose the DCCB, which can lead to severe secondary overcurrents under permanent faults, causing damage to the DC grid. For example, in a 500kV DC grid, such secondary overcurrents can reach up to approximately 10kA. 3. **Reducing the requirement for DCCB continuous breaking capacity**: By reasonably designing the reclosing strategy, the nature of the fault (permanent or non-permanent) can be effectively identified, while limiting secondary overcurrents under permanent faults, thereby reducing the requirement for DCCB continuous breaking capacity. To address the above issues, the paper first analyzes the residual voltage characteristics of mechanical DCCBs under permanent and non-permanent faults and proposes an adaptive reclosing strategy based on these characteristics. This strategy not only reliably identifies the nature of the fault but also effectively avoids secondary overcurrent damage to the system under permanent faults, thereby reducing the requirement for DCCB continuous breaking capacity. The paper also verifies the correctness of the proposed theoretical analysis and the feasibility and superiority of the reclosing strategy through simulation cases based on PSCAD/EMTDC.