Scheme of failure protection for HVDC circuit breakers in MMC-HVDC grid

Fa-xi PENG,Yin-qiu DENG,Zhen WANG,Chao ZHENG,Yun-ting SONG
DOI: https://doi.org/10.3969/j.issn.1001-4551.2017.08.018
2017-01-01
Abstract:Aiming at solving the problem of fast DC-fault clearing in HVDC grid based on MMC ( MMC-HVDC ) , the principle of MMC-HVDC and three main isolation techniques of DC faults were studied. By comparing three technical routes of HVDC circuit breaker ( DC-CB) , the hybrid DCCB was used to interrupt DC faults. The topology and DC fault isolation process of a hybrid DCCB were studied. Refer-ring to the failure protection strategy in AC grid, a scheme of failure protection for HVDC circuit breaker in MMC-HVDC grid was proposed. A four-terminal MMC-HVDC grid was used to verify the feasibility of the proposed strategy in PSCAD/EMTDC platform. The results indicate that the proposed scheme can order adjacent DCCBS to interrupt DC faults completely and clear fault current if a DCCB fails to act.