Protection of Nonpermanent Faults on DC Overhead Lines in MMC-Based HVDC Systems

Xiaoqian Li,Qiang Song,Wenhua Liu,Hong Rao,Shukai Xu,Licheng Li
DOI: https://doi.org/10.1109/tpwrd.2012.2226249
IF: 4.825
2012-01-01
IEEE Transactions on Power Delivery
Abstract:A high-voltage direct current system using modular multilevel converter (MMC-HVDC) is a potential candidate for grid integration of renewable energy over long distances. The dc-link fault is an issue MMC-HVDC must deal with, especially for the nonpermanent faults when using overhead lines. This paper proposed a protection scheme to implement fast fault clearance and automatic recovery for nonpermanent faults on dc lines. By employing double thyristor switches, the freewheeling effect of diodes is eliminated and the dc-link fault current is allowed to freely decay to zero. Then, the dc arc can be naturally extinguished and the insulation on the short-circuit point can be restored. The thyristor switches convert the dc-link fault into an ac short circuit of the ac grid through MMC arms. The ac short-circuit current can be cleared simply by turning off all thyristor switches. Since circuit breakers are not tripped during fault clearance, MMC can immediately and automatically rebuild the dc-link voltage and restart power transmission. Simulation results using PSCAD/EMTDC have verified the validity of the proposed protection scheme.
What problem does this paper attempt to address?