Research on Capacitor Bank Failure Processing Methods
Tong Rui,Liu Jiyong,Wang Ning,Chen Ruiguo,Wang Qinghao,Pang Yanjun,Zhang Bo,Su Hainan,Yang Yue,Wang Enlu,Zhang Wenguang,Liu Chuan
DOI: https://doi.org/10.2991/icmmct-16.2016.274
2016-01-01
Abstract:Aiming to the problem of running with the capacitor bank balance protection action causing tripping, by on-site analysis of the phenomenon and the capacitor discharge coil voltage ratio test checks, secondary coil voltage has relatively large errors caused by the tapped discharge coil. When the system voltage fluctuations, voltage unbalance will break through the setting value, causing balance protection action conclusions; proposed discharge coil tapped in the transfer test or tuning capacitor bank balance protection action value, the voltage ratio between whole primary and secondary should be checked of the discharge coil.