Field Test Study on the New Type of Capacitor Bank Overvoltage Protector

Fan Ye
2007-01-01
Abstract:Since the vacuum circuit breaker may appear the following problems in the switching-in process: the fracture before break-down , the switching-in springing, the switching-in unsynchronism, but in the switching-off process may have the problems such as single phase and two-phase restrike of arc and interception. These problems would cause heavy overvoltage in the process of the vacuum circuit breaker switching capacitor bank. At present, capacitor group overvoltage protector using the I type connection of metallic oxide arrester can't restrict effectively the vacuum circuit breaker coming into being overvoltage because of above-mentioned problems. So works out the new type of capacitor group overvoltage protector. The protector build in parallel connection with the reactance which connect to capacitor group in series, and carries out the field test on switching capacitor group. The results shows: the overvoltage caused by abnormal working condition has been restricted in capacitor bank switching-in process, especially reduces higher extreme overvoltage due to the interception and two-phase arc restriking in capacitor bank switching-off process. The overvoltage protector can absorb the energy of overvoltage in front of due to switching fracture before break-down caused quick wave, the installation of overvoltage protector also inhibites the overvoltage caused.by other capacitor bank switching-in in the system.
What problem does this paper attempt to address?