Fast Transient Test on Capacitor Voltage Transformer with Switching Fixed Series Capacitors Platform Using UHV Disconnector

Jiting Gu,Gongchang Yue,Weidong Liu,Yu Yin,Weidong Shi,Fei Jiao
DOI: https://doi.org/10.13336/j.1003-6520.hve.2014.12.043
2014-01-01
Abstract:Using ultra high voltage(UHV) disconnector to switch the platform of fixed series capacitors(FCSs) may induce fast transient phenomenon and repetitive strikings of the disconnector, and thereby damage adjacent capacitor voltage transformers(CVTs). Hence, we put forward simulative switching tests of switching UHV FSC platform with a disconnector to systematically research the related transient process. In the tests, we measured the overvoltage, transient voltage waveform, and current waveform on CVT, and analyzed the fast transient suppression effect of adding a resistance or an inductance on the high voltage terminal of CVT. The test results show that the maximum overvoltage is about 1.54 times the power-frequency test voltage's peak value, which is much less than the CVT's lightning impulse withstanding voltage, so it is not a serious threat to the CVT. The fast transient current will oscillate with 500 k Hz frequency and 2.2 k A amplitude; the high amplitude and steepness may induce partial overheating and overvoltage in the capacitor elements of CVT, and hence damage the CVT. Adding protection resistance and inductance on the high voltage terminal of CVT shows significant effect in suppressing the amplitude and steepness of fast transient current, consequently well protects CVT.
What problem does this paper attempt to address?