Controllable Multi-stage spark Gap Used in Fast Protection for Series Capacitor Bank

Jianchao ZHENG,Chao ZHANG
DOI: https://doi.org/10.13336/j.1003-6520.hve.2014.12.001
2014-01-01
Abstract:In order to improve the reliability of by-pass protective device for series capacitor bank, we developed a novel controllable spark gap, namely, the frequency-depending multi-stage spark gap driven by Tesla coil. Unlike the existing three-electrode gap that triggers according to operating voltage, the proposed novel gap is independent of the voltage applied on it while working reliably and fast. Through experiments on a prototype, we measured the proposed gap's action characteristics, including its action process, successful action rate, and action duration. The results show that, with reasonable settings, the spark gap has a power frequency withstand voltage of 10 times higher than the operating voltage of series capacitor bank, which prevents any malfunction. Regarding to a protection system using the proposed spark gap, if its action threshold voltage is high enough, its actuation probability will be extremely high that reduces actuation failure and greatly improves the system's reliability. Generally, the actuation time of the protection system will not exceed 20 s, which means a fairly high actuation speed.
What problem does this paper attempt to address?