Experimental Researches on Switching Impulse Corona Characteristics of Conductors Based on Corona Cage

YANG Pengcheng,CHEN Shuiming,HE Jinliang,WUXiong,XU Tao,YE Qiming,GAN Peng,XIE Liang
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2012.34.023
2012-01-01
Abstract:As the nominal voltage of power transmission system rising,switching overvoltage has more and more important effect on the insulation of equipments.How to calculate the switching overvoltage accurately has attracted much more attention.At present,the attenuation and distortion of overvoltage caused by switching impulse corona are ignored in the calculations.Switching impulse corona experiments on the conductors of the type that commonly used in China are carried out in the UHV test base.The results show that the switching impulse corona incepts as the voltage exceeds the inception voltage.Long wave front time switching impulses generate more space charge than standard switching impulse.Positive impulses generate stronger corona than the negative impulses.In the end,controllable breaker is suggested to be used in the transmission lines.As a result,only positive switching corona will be generated and the switching overvoltage will be greatly decreased.
What problem does this paper attempt to address?