Experimental Research on Audible Noise and Radio Interference of Ultra-High Voltage Bundle Based on Corona Test Cage

唐剑,张波,邬雄,万保权,张广洲,张小武
DOI: https://doi.org/10.3969/j.issn.1673-7598.2009.06.002
2009-01-01
Abstract:An ultra-high voltage(UHV) corona test cage has been constructed in the UHV AC test base of SGCC,which is situated in Wuhan.The basic theory and structure of the cage is introduced.The cross-section size and the length of UHV AC cage is 8 m×8 m and 35 m respectively.It can be used to study the corona performance of 1~12 split bundles.The source of test cage is an 800 kV AC test transformer and the simulated maximal voltage level is AC 1 500 kV.The measuring methods for audible noise(AN) and radio interference(RI) of conductor in test cage are analyzed.With the UHV test cage,corona effect of the bundle used in 1 000 kV UHV AC test demonstration project of China is measured.The AN generation power and RI excitation function of UHV bundle are obtained by the UHV cage test data.It supplies the foundation for the prediction of AN and RI of UHV transmission lines in China.