Method to Judge Corona Inception Voltage of AC Transmission Lines Using Corona Cage

CHEN Lan,BIAN Xing-ming,CHEN Feng-lin,MENG Xiao-bo,WANG Li-ming,GUAN Zhi-cheng
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.01.017
2011-01-01
Abstract:The electromagnetic environment directly related to corona phenomena is one of the key technical problems of ultra high voltage(UHV) transmission project.Corona inception voltage is an important parameter to analyze the corona of the power transmission conductors,the judging method of corona inception is not unified.Corona cage is an effective and economical means for duplicating the corona phenomena of the transmission lines by applying lower voltage on the conductor in the cage.Ultraviolet(UV) meter,partial discharge instrument,radio interference receivers,sound level meter-related measurement were used to judge the corona inception voltage.The corona inception voltage from the test was contrasted with the inception voltage calculated by ultraviolet meter of corona cage,and the convenient methods to determine the AC corona inception voltage of conductors were summarized.
What problem does this paper attempt to address?