Measuring DC Corona Inception and Extinction Voltage by Pulse Counts Using UV Corona Monitor

WANG Ke,LIAO Yong-li,WANG Li-ming,GUAN Zhi-cheng,HUO Feng,HU Wei
DOI: https://doi.org/10.13336/j.1003-6520.hve.2010.04.036
2010-01-01
Abstract:In order to guide the design and improvement of grading and shielding rings to meet the requirements of UHV projects in China,research on corona characteristics of these components is needed. A new method to measure DC corona inception and extinction voltage based on UV corona monitor was presented. Measurements of corona inception and extinction voltage on the rob tip in a rob-plate setting under both positive and negative DC voltage were carried out in the laboratory. The same measurements on grading rings with different diameters under positive DV voltage were performed in State Grid Electric Power Research Institute. The results show that this method can be used to obtain the corona inception and extinction voltage.
What problem does this paper attempt to address?